A: If no → check power supply, wiring, fuses.
If yes → move to communication check.
A: Wrong CT/PT wiring will not stop communication, but readings may be incorrect. Ensure CT direction and ratio are correct.
A: Verify baud rate, parity, stop bits, and slave ID in the meter settings. These must match the EnMS software.
A: Yes → check for polarity (A to A, B to B).
No → correct wiring and ensure termination resistor at last device.
A:
If YES → meter is healthy, issue is in EnMS configuration.
If NO → problem in wiring/port/settings.
A: If wrong ID/registers → EnMS cannot read values. Correct as per the MFM manual.
A:
Timeout → wiring/ID/baud mismatch.
CRC error → data corruption due to noise or wrong settings.
Device not found → wrong IP/ID or device offline.
A: Faulty converters or driver issues can stop communication. Replace/test with another converter.
A: Very short polling may cause a data timeout. Set 5–10 seconds polling.
A: If all settings are correct and Modscan also fails, → meter port may be damaged. Replace or repair.
✅ Final Checklist for Client:
Meter powered and displaying locally
CT/PT wiring is correct
RS-485/Ethernet wiring correct & terminated
Baud rate/parity / stop bits / ID matched
Test with Modscan/Modpoll
Verify EnMS configuration (ID, IP, registers)
Check the converter/network device
Review EnMS logs for error type